ZENO
®
-3200 USER MANUAL
Coastal Environmental Systems (206) 682-6048
Page 52
If you need to adjust the internal ZENO
®
-3200 clock backward, to avoid
data records with overlapping timestamps, Coastal Environmental Systems
recommends that you either:
1. Only set the clock back to a time not earlier than the timestamp of the
most recent logged data record, or
2. If you need to set the internal clock to a time earlier than the timestamp
of the most recent logged data record, first download all logged data
records to your computer, then delete all the logged data records.
4.1. DATA RETRIEVAL OPTIONS
There are several different ways you can retrieve logged data records from your ZENO
®
-3200. The
various options include:
Retrieve the most recently logged data records
Retrieve the oldest (unmarked) logged data records
Retrieve all logged data records at once
Retrieve logged data records after a specific date and time
Retrieve logged data records between two consecutive dates & times
View the logged data records in your terminal emulation program
Download the logged data records into a computer using simple ASCII or the X-modem protocol
From the User Interface Menus, all logged data retrieval is done via the Data Retrieval Menu. Type
D{ENTER} from the User Menu to enter the Data Retrieval Menu.
Your screen will look something like this:
DATA RETRIEVAL MENU
(A) Show Records AFTER Specified Time (C) Compute Data Logging Capacity
(B) Show Records BETWEEN Timespan (D) Delete All Data Records
(Ln) Show LAST n Records (N) Number of Records Logged
(*) Show ALL Data Records (U) User Menu
(@n) Show n Unmarked Records (Q) Quit
(M) Mark Recently Shown Data (H) Help
Precede Any "Show Data" Command With An 'X' for X-Modem Transfer
(eg. Enter 'X*' To Send All Data Sets Via X-Modem)
When you retrieve logged Data Records using the Data Retrieval Menu, all Data Records displayed will
include the timestamp (date & time) when the Data Record was logged followed by the actual data
contained in each Data Record.