Coastal Environmental Systems (206) 682-6048 Page D-35
The Missing Sensor Data Process allows the setting of an alarm condition when the inputted data value is
set to a BSV and allows replacement of a BSV with a substitute value. The first data output from this
process is the alarm condition, which is set to one if the inputted data value is a BSV; otherwise, it is set
to zero. The second data output is the inputted data value (Line Item #4) when it is NOT a BSV;
otherwise, it is the substitute, default value specified by Line Item #5.
3.9. Multiple Alarm Process
Inputs: 4-11 Data inputs, preferably from other alarm processes (D)
12 Number of input alarms required for output alarm (U)
13 Digital I/O port number, 18 to 23 (U)
14 Digital I/O port number, 18 to 23 (U)
15 Output Message Number, 1 to 4 (U)
16 Log Alarm Message, 0 = no or 1 = yes (U)
Outputs: 1 Status
0 no alarm condition
1 alarm condition
E1 Process Error Code
Assumptions: Input numbers 1 through 8 are alarm inputs
Activates a digital output (5 VDC), and initiates modem dial-out, on
certain combinations of alarm conditions (see below)
The Multiple Alarm Process allows the user to define an alarm condition that is the result of a
combination of conditions. Up to eight individual input values can be referenced by Line Items #4
through #11. Each of the input values is interpreted in a Boolean fashion: 1) no condition exists if the
input value is zero or 2) the condition does exist when the input value is non-zero. Line Item #12 defines
how many (N) existing conditions from Line Items #4 through #11 constitute an alarm condition.
Here is an example of four separate conditions:
Let Line Item #4 reference an alarm process triggered when the temperature goes below freezing
Let Line Item #5 reference an alarm process triggered when the wind speed exceeds 25 knots
Let Line Item #6 reference an alarm process triggered when the air temperature drops below the
dewpoint
Let Line Item #7 reference an alarm process triggered when the barometric pressure drops below 30
inches of mercury
To continue the example, an alarm condition does not need to be reported when only one or two of the
listed conditions exists; but an alarm condition does need to be reported if at least three conditions exist
simultaneously. Therefore, Line Item #12 would be set to 3 and the Multiple Alarm Process will be
triggered when at least three of the four conditions is present.
When the Multiple Alarm Process determines that an alarm condition exists, data output #1 will be set to
one; otherwise, it is set to zero.
The digital outputs, switched voltage and logging an alarm message
358
are set slightly differently from
data output #1. If less than N of the input values is non-zero, then the digital outputs (if defined) and
switched voltage (if defined) are set low. The first time that N or more input alarms are non-zero, if