Coastal Environmental Systems (206) 682-6048
Page 179
10.4.5. Process Error Checking and Reporting
Sometimes, the ZENO
®
-3200 cannot collect data from sensors for one or more reasons:
Disruption in serial communication with a serial sensor
Insufficient time to collect data from all configured sensors
200
Poor electrical connections to a sensor
When the ZENO
®
-3200 cannot collect data from a particular sensor, the output of that sensor will be set
to a specific value that indicates invalid data:
-1,000,000 for floating-point data
0xffffffff for long integer data
a null string
201
for string data
-1,000,000 or 0xffffffff is referred to as a Bad Sensor Value or “BSV.”
ZENOSOFT
®
was enhanced to prevent processes from erroneously processing invalid data.
Any process that inputs data from a Sensor or a previous Process Record
that is a BSV will NOT use the BSV in its calculations. Instead, the process
will ignore the BSV and output BSVs of its own, or leave its data unchanged
depending upon the nature of the process.
As a general rule, any process that accumulates data over time to calculate its outputs will simply ignore
BSVs and leave its own data unchanged, but any immediate data outputs will be set to BSVs.
To report that an error has occurred in a process, every process has an extra error output designated as
output E1. E1 is a long integer output. The following types of errors are reported in error output E1:
Bit Meaning
1 Process not evaluated during sample interval.
2 Input data is out of range.
3 Input data is a Bad Sensor Value (BSV, -1,000,000 or 0xFFFFFFFF).
4 Input data is intermittently bad or out of range during sample interval.
5 Input data is questionable (from a process reporting an error).
6 User input data out of range.
7 Internal error (meaning depends upon process).
8 Not defined.
When a process receives a BSV, it will set bit 3. If the process receives the BSV more than once during a
sample interval, it will also set bit 4. If an input to a process has a limited range of acceptable values, and
200
This is usually the result of an incorrect configuration.
201
A null string is a string containing no characters. It has a length of zero.