ZENO
®
-3200 USER MANUAL
Coastal Environmental Systems (206) 682-6048 Page D-32
Assumptions: If the Alarm Reset value is less than the Alarm Set-point value then the
alarm is activated when the data value becomes greater than the Alarm
Set-point, and deactivated when it goes below the Alarm Reset
If the Alarm Reset value is greater than the Alarm Set-point value then
the alarm is activated when the data value drops below the Alarm Set-
point, and deactivated when it returns above the Alarm Reset value
This process reads the data input, compares it to the Alarm Set-point and Alarm Reset values, and
activates or deactivates the alarm status accordingly.
If the alarm is set, the corresponding bit in the global BIT value will be set.
348
Any digital output
specified by Line Items #8 or #9 will be set HIGH. Any switched voltage specified by Line Item #10 will
be turned on.
3.4. Data Time-out Process
Inputs: 4 Any sensor or process output
5 Time-out Interval (seconds)
6 Minimum Delta Change
7 BIT bit number (1 to 31, 0 = disabled)
Outputs: 1 Status
0 data has changed within the time interval
1 data has not changed
E1 Process Error Code
Assumptions: None
The Data Time-out Process is an excellent tool to check for faulty sensors or malfunctioning system
components because the process observes how much the input data changes over time:
The input data is read and compared to a baseline reading.
If the difference between the two values is greater than the Minimum Delta Change value, then a new
baseline level is established as the current data reading, and the time elapsed counter is reset.
Otherwise, if the difference is less than the Minimum Delta Change, then the time elapsed counter is
compared to the Time-out Interval. If the time elapsed is greater than the Time-out Interval then the
output status is set to 1 and a bit flag may be set in the global BIT value
349
.
This process is similar to the Static Alarm Process.
350
3.5. Alarm Reset Process
Inputs: 4 Digital I/O port number (18 to 23)
5 Second digital I/O port number (18 to 23)
Outputs: E1 Process Error Code
Assumptions: A reset button provides a switch closure input to channel 24, the IRQ4
channel; this cannot coexist with a tipping bucket sensor which requires
the same input channel
348
Refer to Category #3, Process #1.
349
Refer to Category #3, Process #1.
350
Refer to Category #3, Process #15.