ZENO
®
-3200 USER MANUAL
Coastal Environmental Systems (206) 682-6048
Page 198
10.6.10. Selecting Data To Log & Transmit Via Output Message Number
When you configure the ZENO
®
-3200 to output more than one output message, you can configure single
data fields within each output message to contain different data based upon the output message number.
This is done using the Selectable Log and Transmit Field Type Code in a Data Output Record.
The ZENO
®
-3200 WILL ONLY LOG extra output messages when the Dial-
out Alarm Process or Multiple Alarm Process is included in the
configuration and set up to log a specific output message!
You cannot configure different output messages to log different numbers of
data values. Each output message that logs unique data will log the same
number of data values.
When you configure a Data Output Record using the Selectable Log and Transmit Field Type Code, the
Data Output Record will look something like this:
DATA OUTPUT MENU
(Cn/m) Change Item n To Value m (Jn) Jump To Record n
(A) Insert After This Record (N) Go To Next Record
(B) Insert Before This Record (P) Go To Previous Record
(X) Cut Record to Clipboard (XA) Delete ALL Records
(C) Copy Record To Clipboard (Z) Zeno Program Menu
(V) Paste Record From Clipboard (H) Help
(Sn/m) Search Item n for Value m
Data Items for Record 2 of 22:
Item 1: Field Type Code 15 : Selectable Transmit and Log Field
Item 2: Output Message(s) 1,2,3
Item 3: Field Name MsgId
Item 4: Msg 1 Input Record P8.1 : SelectID
Item 5: Field Decimal Places 0
Item 6: Field Width 0
Item 7: Data Storage Class Code 3 : 2-byte signed integer
Item 8: Msg 2 Input Record C2
Item 9: Msg 3 Input Record C3
Item 10: Msg 4 Input Record C4
>
In this example, when Message #1 is generated, ZENOSOFT® will select output #1 from Process Record
#8 to both transmit and log. When Message #2 is generated, ZENOSOFT
®
will select the value of
constant C2 to both transmit and log. When Message #3 is generated, ZENOSOFT
®
will select the value
of constant C3 to both transmit and log. Since Message #4 is not specified in the Output Messages (Item
2), constant C4 would NOT be selected if Message #4 were generated; instead, ZENOSOFT
®
would use
the same value as selected for Message #1 (the default message number).