DIGITAL CONTROL MENU
(Cn/m) Change Item n to Value m (E) Save Parameters To EEPROM
(U) User Menu (Q) Quit
(H) Help
Item 1: 000:00:00 (Power-On Interval)
Item 2: 000:00:00 (Power-On Duration)
Item 3: 96/01/01 00:00:00 (Start of First Power-On)
Item 4: 0 (Control Channel)
>
Each Digital Output is active when it is LOW and inactive when it is HIGH.
This is called “negative logic.”
Line items 1, 2, and 3 allow you to set the schedule at which a Digital Output will be set LOW. If
connected to a relay, it will control the action of the relay. The schedule is independent of the Sample
Interval definition:
Digital
Output Menu
Line Item No. Name Definition
1 Power-On Interval Defines how frequently the Digital Output will be
turned on.
2 Power-On Duration Defines how long the Digital Output will be on each
time it is turned on.
3 Start of First Power-On Defines when initial starting time of the cycle.
Similar to an offset.
For example, the Digital Output could be switched on for the first 5 minutes of every hour to turn on a bi-
directional radio, while the Sample Interval calls for a new measurement every 10 minutes. A Power-on
Interval and Power-on Duration of up to 168 hours (7 days) can be entered in the format hhh:mm:ss.
Power-on corresponds to the Digital Output set LOW; power-off to the Digital Output set HIGH.
Valid values for Line Item #4, the Digital Control Output, are 18 through 23, corresponding to the Digital
Outputs on the ZENO
®
-3200 Front Panel
121
. If you set Line Item #4 to 0 (or if you set Line Item #1, the
Power-on Interval to 000:00:00), then the Digital Control Output will be disabled (as the above example
of the Digital Control Menu shows).
121
Refer to Section 2.1.