ZENO
®
-3200 USER MANUAL
Coastal Environmental Systems (206) 682-6048 Page C-26
ITEM DATA
COMMAND ENTERED
Item 1: Process Category Code = 5 : Arithmetic C1/5
Item 2: Process Type code = 3 : Add Data Values Process C2/3
Item 3: User-defined Process Name = 3 : AddFlag c3/AddFlag
Item 4: Input for Augend (X) = P1.1 : Miss425
6
C4/P1.1
6
Item 5: Input for Addend (Y) = P2.1 : Prev
6
C5/P2.1
6
DEFAULT = Default value: it is not necessary to enter a command for this item.
6 This value will vary depending on the number of sensors being connected to the ZENO
-3200.
Settings to Collect Data From Vaisala 425AH Sensor on COM2
ITEM DATA
COMMAND ENTERED
Item 1: Process Category Code 2 : Environmental
C1/2
Item 2: Process Type code 1 : Wind Vector Average DEFAULT
Item 3: User-defined Process Name = 3: AvgWind
c3/AvgWind
Item 4: Input for Wind Speed S1.1 : 425AH
7
C4/S1.1
7
Item 5: Input for Wind Direction S1.2 : 425AH
7
C5/S1.2
7
Item 6: Input for Compass S0.1 (Not specified)
8
DEFAULT
DEFAULT = Default value: it is not necessary to enter a command for this item.
7 This data will vary depending on the number of sensors being connected to the ZENO
-3200.
8 If a serial compass is included, specify the output from the Sensor Record specifying the compass. Also, Line
Items #5 and #6 from the System Functions Menu will need to be specified (refer to Section 5.7).
DATA OUTPUT MENU
Settings to Collect Data From Vaisala 425AH Sensor on COM2, Average Wind Speed
ITEM DATA
COMMAND ENTERED
Item 1: Field Type code = 9 : Transmit and Log Data Field
c1/9
Item 2: Output Message(s) = 1 DEFAULT
Item 3: Field Name = WS
c3/WS
Item 4: Data Process Record = P4.1 : AvgWind
9
c4/P4.1
9
Item 5: Field Decimal Places = 1
c5/1
Item 6: Field Width = 5
c6/5
Item 7: Data Storage Class Code = 7 : Compressed Floating Point (2)
c7/7
DEFAULT = Default value: it is not necessary to enter a command for this item.
9 This value will vary depending on the number of sensors being connected to the ZENO
-3200. Further, if you
want scalar average wind speed instead of vector average wind speed, use data output #3; i.e., P4.3.