ZENO
®
-3200 USER MANUAL
Coastal Environmental Systems (206) 682-6048 Page C-19
ITEM DATA
COMMAND ENTERED
Item 1: Sensor Type code = 16 (General Serial Script)
c1/16
Item 2: Sensor Name = ceil
c2/ceil
Item 3: Sensor Input Channel = COMPASS INTERFACE
c3/COMP
Item 6: Switched Power code = 1 (5V SW'D A)
C6/1
Item 9: Sensor Warm up Time = 220
C9/220
Item 10: Sensor Sample Count = 1 DEFAULT
Item 11: Maximum Sensor Readings = 10
C11/10
Item 12: Sensor Timing Loop = 3 (17 seconds)
c12/3
Item 16: Retry Count = 4
C16/4
Item 17: Sensor Address = 0 DEFAULT
Item 18: Sensor Port Type = RS232 DEFAULT
Item 19: Sensor Baud Rate = 1200
C19/1200
Item 20: Sensor Bits Per Character = 8 DEFAULT
Item 21: Sensor Parity = N DEFAULT
Item 22: Sensor Start Bits = 1 DEFAULT
Item 23: Sensor Stop Bits = 1 DEFAULT
Item 24: Sensor GSI Script Number = 1 DEFAULT
Item 25: Sensor Data Collection Control = S0.1 DEFAULT
DEFAULT = Default value: it is not necessary to enter a command for this item.
SENSOR TIMING LOOP MENU
ITEM DATA
COMMAND ENTERED
Item 1: Timing Loop #1 Period = 0.5 DEFAULT
Item 2: Timing Loop #2 Period = 1 DEFAULT
Item 3: Timing Loop #3 Period = 17
c3/17
Item 4: Timing Loop #4 Period = 2 DEFAULT
DEFAULT = Default value: it is not necessary to enter a command for this item.
GENERAL SERIAL SCRIPT MENU
LINE DATA
Line 1 STRING 4 ( 90, 1, 2, 4 )
Line 2 FLOAT 9
Line 3 RECEIVE 1000, "%s", S1
Line 4 SEND "FL\r"
Line 5 WAIT 10
Line 6 RECEIVE 5000, "%s", S1
Line 7 RECEIVE 0, "%s,%f,%f,%f,%f,%f,%f,%f,%f,%s,%f,%s,", S2, F1, F2, F3, F4, F5, F6, F7, F8, S3, F9,
S4