D-1
Appendix D. COM210 to CR510PB-
Router to 10 CR205s Network
In this configuration LoggerNet does 15 minute scheduled collections from
remote CR205s via COM210 dialed link and a CR510PB configured as router.
Hardware Setup
PC----(PC modem)-----------------------COM210--CR510PB--RF400~~~~~~~~~~~CR205_1
~~~~CR205_2
~~~~CR205_3
…
LoggerNet Device Map
ComPort_1
PhoneBase
PhoneRemote
PakBusPort
CR510PB (PakBus Address = 100)
CR205_1 (PakBus Address = 1)
CR205_2 (PakBus Address = 2)
CR205_3 (PakBus Address = 3)
… (PakBus Address = n)
In the PakBusPort screen configure beaconing for 0 seconds. LoggerNet will
find the CR510PB as a static route from its device map. The first time you dial
and connect, PakBusGraph will show the CR510PB and the CR205 neighbors
to the CR510PB.
LoggerNet Schedule Tab
Collection Interval – 15 minutes
Primary Retry Intervals – 5 minutes
Number of Primary Retries – 2
Secondary Retry Interval – 60 minutes
RF400 Settings
In a PakBus rf network all radios are configured for the same radio address,
network address, and hopping sequence. Device selection is accomplished
using the unique PakBus addresses assigned to the PakBus devices
(dataloggers).
1. Configure RF400 with the same Radio Address, Net Address, and
Hopping Sequence as the CR205s have. If there will be no other RF400
radios within range, you can use default settings.
2. Other settings
Active Interface = “CSDC” (7 by default but could be 8)
Standby Mode = “< 24 mA always on”