Appendix F. CR510PB w/ P193 Master to CR205s Network
F-2
Hardware Setup
P193
PC
LoggerNet
modem
COM210
CR510PB_100
CR205_2
CR205_3
CR205_1
CR205_4
CR205_5
RF400
CSDC 7 Por
LoggerNet Device Map
ComPort_1
PhoneBase
PhoneRemote
PakBusPort
CR510PB (PakBus Address = 100)
CR200_1 (PakBus Address = 1)
CR200_2 (PakBus Address = 2)
CR200_3 (PakBus Address = 3)
CR200_4 (PakBus Address = 4)
CR200_5 (PakBus Address = 5)
After once dialing up and connecting in LoggerNet, PakBusGraph will display
the CR510PB and its CR205 neighbors.
LoggerNet Schedule Tab
Collection Interval – 15 minutes
Primary Retry Intervals – 5 minutes
Number of Primary Retries – 2
Secondary Retry Interval – 60 minutes
RF400 Settings
In a PakBus rf network, all RF400 Series radios are set up the same, except
possibly the ports (Active Interfaces).
1. Configure RF400 radio with the same radio address, network address, and
hopping sequence as the CR205s. If there will be no other RF400s in the
area, you can use default settings, otherwise, choose some other hopping
sequence, network address, and radio address and configure all radios in
the network alike.
2. Other Settings
Active Interface = “CSDC 7” (Port 7 is the default. Port 8 could be used)