Seitenansicht 52
PakBus Networking Guide
47
Remarks
The TimeUntilTransmit value is derived from the time slot information that is
sent by the host datalogger. If the host datalogger has not yet sent time slot
information, this instruction will use a random time interval between 0 and 60
seconds until communications with the host is established.
Parameter
Port
The Port parameter is used to specify the CR200 Series com port that will
be used for communications. Enter a numeric code:
Code Description
1RF
2 RS232
7. PakBus Concepts
7.1 PakBus Device
A PakBus device is a device with processor/software that allows it to
communicate using CSI’s PakBus packet protocol. Some examples of devices
configurable as PakBus devices are: LoggerNet server, CR10X, CR23X,
CR510, CR205, and NL100. The indicated dataloggers must have a PakBus
OS to be a PakBus device, however, the CR205 and the soon-to-be-announced
CR1000 are native PakBus devices. In this guide the term “device” is often
used as an abbreviation for “PakBus device.”
BMP5 (Block Mode Protocol 5) is a datalogger application protocol that rides
on top of PakBus.
Each PakBus device in a network must have a unique PakBus Address in order
for the network to function properly.
7.1.1 PakBus Address
The term “PakBus Address” is equivalent to PakBus ID, node ID and node
address. The preferred term is PakBus Address. Every PakBus device needs a
PakBus Address in order to receive, send, or route PakBus packets.
LoggerNet’s default PakBus Address (“PakBus Computer ID”) is 4094 and its
allowable range is 1 to 4094. PakBus devices have default PakBus Addresses
(usually “1”) that you can edit as needed.
7.1.2 Node
In PakBus networking a “node” is equivalent to a “PakBus device.” The
LoggerNet server, a PakBus datalogger, and an NL100 can all be configured as
a PakBus node.