PakBus Networking Guide
68
8.5 Rapid spurious communications lasting a few seconds at a
time between devices in RF400 network.
Possible reason
Two network devices have the same PakBus Address.
Remedy
Change one of the duplicate PakBus Addresses. Make all addresses unique
throughout the network.
8.6 In P193 network, certain CR200 Series devices don’t
transfer data.
Possible reason
The Master datalogger’s *D15 setting configures too few max nodes, max
neighbors, and max routers.
Remedy
Change Master *D15 settings for max nodes, max neighbors, and max routers
to larger numbers reflecting the network size.
*D15 settings allocate memory similar to *A. It is a good
idea, when configuring *D15 settings, to leave ‘room to
grow.’
Changing *D15 settings later on could result in loss of data.
CAUTION