November 2005, ARM-TR-069
F-2
2. Strike the Enter button a few times to get the attention of the NL-100 once the following is
returned you may continue:
NL100/105 (ver, show, edit, defaults, reset, help, bye):
3. Type E to Edit and make sure the following is set:
Tlink config [dis]
RS485 [dis]
CS I/O [dis]
RS232 Config [TCPServ]
RS232 bps [19K]
RS232 Serial Server Port [6781]
Ethernet 10-baseT [enabled]
10-baseT port IP# [198.124.98.19]
*
this value is logger IP address
mask [255.255.255.0]
*
whatever mask is used
default gateway [yes]
default gateway IP [198.124.98.1]
Pakbus node [678]
Clock neighbor node ID [0]
PakTcp Server config [dis]
PakTcp client config [dis]
Modbus/Tcp gateway config [dis]
Config monitor telnet port [23]
Telnet Session password [nl100]
Serial Server Watchdog [2]
Save
You can progress through the menu by pressing <ENTER>. If you make a mistake after entering
a setting, the up arrow can be used to move backwards. If you need help for a particular setting,
press the F1 key or the ? key. You can also choose to select <cancel> at the end instead of save if
you want to start over.
*
If the jumper was used it must be disconnected before returning the NL-100 to use. If this is not done, the
NL-100 will always be at the boot prompt and will be inaccessible for remote communications.