Appendix D. Setting Up RF401-to-
CR206(X) Communications
Certain CR206(X) settings must match the RF401 settings for communications
between the datalogger and radio to be successful. The factory default settings
of these devices may not match.
D.1 CR206(X) Setup Information
1. Access the Deployment panel in DevConfig (see Figure D-1).
FIGURE D-1. CR206 Setup Main Menu
2. PakBus Address: Must match the PakBus Address in LoggerNet.
3. RF Protocol: Select PakBus Aware if the RF401s and RF430s in your
network are set to PakBus Aware or PakBus Node. The Transparent
setting must be used if your network includes CR205 dataloggers or
RF400 radios. If Transparent is used, all dataloggers and radios in the
network must be set to Transparent.
4. Hop Sequence: Must match all of the RF401 and RF430 radios and other
CR206(X) dataloggers in the network.
D-1