3.7 Climate Station Pre-installation Preparations
Once a suitable location for the climate station has been found, preparations need to be made to
the terrain before the infrastructure and the sensors are installed. These guidelines apply to the
main climate station.
Clear the terrain: Clear a small core area (60-65 m
2
) where the climate station with all its
instrumentation will be installed. This area could be circular or rectangular, but most
importantly, it needs to be devoid of all vegetation, with a very short layer of grass or whichever
the natural substrate is in the area; no rock, asphalt or cement.
3.8 Tripod Installation
Assemble the CM10 tripod kit as described in the manual supplied by Campbell (also online at
http://www.campbellsci.com/documents/manuals/cm10k.pdf).
3.9 Grounding
PROPER GROUNDING IS CRITICAL TO PROTECT THE INTEGRITY OF ALL THE
EQUIPMENT against lighting strikes. First drive the grounding rod into the ground as far as it
will go next to the base of the tower (about half a meter away) using a sledgehammer. At most,
there should only be 3 or 4 centimeters of the rod visible above ground. Attach one end of
the ground cable (4 AWG wire) to the rod and then route the cable and attach to the tower leg
using the clamp. Route the green (12 AWG ) wire upwards to where the instrument enclosure
will be installed (see more details in page 2-3 of the UT10 manual). See Section 3.18 for details
on grounding the enclosure and the data logger.
3.10 Installing the Data Logger and Battery
Equipment/supplies needed:
• Wrench
• Screwdriver
• Data Logger (CR1000)
• Enclosure (ENC 14/16-C)
• Battery (UB121000)
• Plastic/metal container
Data logger: The data logger (CR1000) should be installed in a weather resistant enclosure that
is attached to the side of the tripod (ENC 14/16-C). First install the data logger into the enclosure
and then attach the enclosure to the tripod. The data logger should be mounted low in the
enclosure and secured to the backplate with 4 screws. This should leave plenty of space below
the data logger for the incoming cables from the sensors and power source as well as the ground
cable. The enclosure can be mounted to the tripod by using the attached mounting brackets.