MicroMet MBTU10X Version 1.05 Installation and Operation Manual Revised 4.26.02 Micro Specialties, Inc. P.O. Box 871077 Wasil

Seite 2

MicroMet Manual Pg. 7 Operation MicroMet Observations. The top MicroMet printed circuit board has five Light Emitting Diodes (LED) That can tell

Seite 3

MicroMet Manual Pg. 8 MicroMet Commands - MBTU10X Rev 1.05 The Micromet command structure is simple and concise. All commands are terminated wi

Seite 4 - About MicroMet

MicroMet Manual Pg. 9 T – Test transmission. MicroMet will turn on its transmitter and attempt to send whatever is in its immediate transmit queu

Seite 5 - MicroMet Manual Pg. 2

MicroMet Manual Pg. 10 Warnings and Advisories MicroMet may issue various advisories or warnings to indicate a change in system status. Advisori

Seite 6 - MicroMet Manual Pg. 3

MicroMet Manual Pg. 11 Communications Cycle MicroMet MBTU10X operates as a power conserving remote node in a ‘star’ network topology. The networ

Seite 7 - Installation

MicroMet Manual Pg. 12 Understanding Communications Statistics (Stat Command) RXSP Signal Presence – this is the number of times the radio recei

Seite 8 - MicroMet Manual Pg. 5

MicroMet Manual Pg. 13 HIVSWR High Voltage Standing Wave Ratio – this means that during a transmit cycle, MicroMet’s transmitter hardware dete

Seite 9 - MicroMet Manual Pg. 6

MicroMet Manual Pg. 14 Checking MicroMet Communications Performance 1. Connect the MicroMet cable between the PC and J3 of the MicroMet unit. 2.

Seite 10 - Operation

MicroMet Manual Pg. 15 CR10X Datalogger Operations Loading a CR10X program from PC208W When a new program needs to be installed in the CR10X dat

Seite 11 - MicroMet Manual Pg. 8

MicroMet Manual Pg. 16 Setting up a New Data Station in PC208W PC208W is Campbell Scientific’s CR10X maintenance program that runs under Windows.

Seite 12 - MicroMet Manual Pg. 9

Index Conventions Used in Manual 1 About MicroMet 1 CR10X Processing for MicroMet 3 Installation Site Selection

Seite 13 - Warnings and Advisories

MicroMet Manual Pg. 17 Verifying Sensor Data with PC208W Campbell Scientific’s Windows based Data Logger maintenance program, PC208W can be used

Seite 14 - Communications Cycle

MicroMet Manual Pg. 18 Site Visit Normal Site Visit Procedures Whenever a visit is made to a MicroMet data site, the following checks should be

Seite 15 - MicroMet Manual Pg. 12

MicroMet Manual Pg. 19 Troubleshooting No Data Reports Received at AMBCS Before troubleshooting, read and understand MicroMet Observations (pg 6

Seite 16 - MicroMet Manual Pg. 13

MicroMet Manual Pg. 20 No CR10X Data Messages ! If you suspect that the CR10X is not producing any data messages, you should connect your PC to

Seite 17 - MicroMet Manual Pg. 14

MicroMet Manual Pg. 21 Resolving Bad Sensor Readings (CR10X) ! Connect your PC to CR10X CSIO, and run PC208W. ! Use the NUMERIC DISPLAY tab

Seite 18 - CR10X Datalogger Operations

MicroMet Manual Pg. 22 Replacing the CR10X Data Collector Canister The CR10X Data Collector is the unit which interfaces to, and collects data f

Seite 19 - MicroMet Manual Pg. 16

MicroMet Manual Pg. 23 Installing the new CR10X canister ! Examine the replacement CR10X canister. Notice that it has two connector plugs which

Seite 21 - Site Visit

MicroMet Manual Pg. 25 CR10X Files All CR10X files are maintained by Campbell Scientific’s PC208W program. PC208W usually installs files in the

Seite 22 - Troubleshooting

MicroMet Manual Pg. 26

Seite 23 - No CR10X Data Messages

Troubleshooting No Data Reports Received at AMBCS 19 No CR10X Data Messages 20 Resolving bad Sensor Readings (CR10X) 21 Replaci

Seite 24 - MicroMet Manual Pg. 21

MicroMet Manual Pg. 1 Conventions Used in This Manual MicroMet and CR10X commands are printed in bold face for clarity. ‘Warning:’ indicates tha

Seite 26 - MicroMet Manual Pg. 23

MicroMet Manual Pg. 3 CR10X processing for MicroMet Version 1.03 and above The CR10X, when used with the MicroMet MBTU10X for data transport, mu

Seite 27 - MicroMet Manual Pg. 24

MicroMet Manual Pg. 4 Installation Site Selection Considerations Communications Window Aperture What is the horizon in the direction of radiati

Seite 28 - CR10X Files

MicroMet Manual Pg. 5 Installing the MicroMet Communications Unit MicroMet data communications units come in two varieties, one with a 300 watt t

Seite 29 - MicroMet Manual Pg. 26

MicroMet Manual Pg. 6 Setting up a Windows95/98 Computer to talk with the MicroMet Normal operation of the MicroMet unit is fully automatic, and