
User Manual
5
Figure 4-2. 2-wire with external power
4.1.1 Possible Ground Loop Problems
The resistor must be grounded at the datalogger to ensure that measurements are
within common mode range. The signal (or low) output on the transducer is
higher than the datalogger ground by the voltage drop across the resistor. A
ground-loop error may occur if the signal output is not electrically isolated but is
connected to the sensor's case. If such a sensor is in contact with earth ground (for
example, a pressure transducer in a well or stream), an alternative path for current
flow is established through earth ground to the datalogger earth ground. This path
is in parallel with the path from the signal output through the resistor; hence, not
all the current will pass through the resistor and the measured voltage will be too
low.
4.1.2 Minimum Supply Voltage
When the power supply is in the current loop, as is the case in a 2-wire transducer,
it is necessary to consider the effect of voltage drop across the resistor on the
voltage applied to the transducer.
For example, suppose a 4 to 20 mA transducer requires at least 9 volts to operate
correctly and the system is powered by a 12 volt battery. The voltage the
transducer sees is the battery voltage minus the voltage drop in the rest of the
current loop. At 20 mA output, the voltage drop across the 100 ohm resistor is 2
volts. When the battery is at 12 volts, this leaves 10 volts for the transducer and
everything is fine. However, if the battery voltage drops to 11 volts, a 20 mA
current will leave just 9 volts for the transducer. In this case, when the battery
drops below 11 volts, the output of the transducer may be in error.
Figure 4-3. 2-wire supply voltage
Kommentare zu diesen Handbüchern