Section 7. Measurement Instructions
Parameter
& Data Type
Enter
Value Description
1 Retrieve data; unsigned integer, most significant byte first
2 Retrieve data; unsigned integer, least significant byte first
3 Retrieve data; signed integer, most significant byte first
4 Retrieve data; signed integer, least significant byte first
5 Retrieve data; 4-byte IEEE floating point number; most
significant byte first
6 Retrieve data; 4-byte IEEE floating point number; least
significant byte first
7 Build data frame in SDM-CAN memory; unsigned integer, most
significant byte first. Overwrite existing data.
8 Build data frame in SDM-CAN memory; unsigned integer, least
significant byte first. Overwrite existing data.
9 Build data frame in SDM-CAN memory; signed integer, most
significant byte first. Overwrite existing data.
10 Build data frame in SDM-CAN memory; signed integer, least
significant byte first. Overwrite existing data.
11 Build data frame in SDM-CAN memory; 4-byte IEEE floating
point number; most significant byte first. Overwrite existing
data.
12 Build data frame in SDM-CAN memory; 4-byte IEEE floating
point number; least significant byte first. Overwrite existing
data.
13 Build data frame in SDM-CAN memory; unsigned integer, most
significant byte first. Logical "OR" with existing data.
14 Build data frame in SDM-CAN memory; unsigned integer, least
significant byte first. Logical "OR" with existing data.
15 Build data frame in SDM-CAN memory; signed integer, most
significant byte first. Logical "OR" with existing data.
16 Build data frame in SDM-CAN memory; signed integer, least
significant byte first. Logical "OR" with existing data.
17 Build data frame in SDM-CAN memory; 4-byte IEEE floating
point number; most significant byte first. Logical "OR" with
existing data.
18 Build data frame in SDM-CAN memory; 4-byte IEEE floating
point number; least significant byte first. Logical "OR" with
existing data.
19 Transmit data value to the CAN-bus; unsigned integer, most
significant byte first.
20 Transmit data value to the CAN-bus; unsigned integer, least
significant byte first.
21 Transmit data value to the CAN-bus; signed integer, most
significant byte first.
22 Transmit data value to the CAN-bus; signed integer, least
significant byte first.
23 Transmit data value to the CAN-bus; 4-byte IEEE floating point
number; most significant byte first.
24 Transmit data value to the CAN-bus; 4-byte IEEE floating point
number; least significant byte first.
25 Transmit previously built data frame to the CAN-bus.
26 Set up previously built data frame as a Remote Frame Response.
7-32