CAUTIONARY
NOTES
1. To
prevent
corrosion in the CR500,
desiccant
must be
placed
inside
the
enclosure.
To reduce vapor transfer
into the
enclosure,
plug
the cable
entry
seals.
DO
NOT
totally seal enclosures
equipped
with
lead
acid
batteries. Hydrogen
concentration
may
build
up to explosive
levels.
Damage
will occur to the
analog
input
circuitry
if voltages
in
excess
of
+16
V are
applied
for
a sustained
period.
Voltages
in
excess
of 15 V will cause
errors
and
possible
overranging
on other
analog
input
channels.
When
using the CR500
with the
PS12LA,
remember
that the sealed
lead
acid
batteries
can be
permanently
damaged
if
deep
discharged
routinely
or left
in
a
discharged
state
for a
long
period
of time.
The cells
are
rated
at
a 7 Ahr capacity
but
experience
a
slow discharge
even
in
storage.
lt is advisable
to maintain
a
continuous
charge on
the PS12LA
battery
pack,
whether
in operation or
storage.
To
make it easier to
connect
power
to the
CR500
remove
the
green
connector
on the
terminalstrip.
Connect
12 V and
G in the
proper
positions
and
plug
the
connector
back
into its receptacle.
When
connecting
power
to
the
CR500
with
the
green
connector
in
place,lirst
connect
the
positive
lead
from the
power
source to
the
12 V terminal.
Then connect
the
negative
lead to G. Connecting
these leads
in
the
reverse order
makes
it easier
for
the
positive
wire
to accidentally
touch
a
grounded
component
and
short
out the
power
supply.
Voltages
in
excess of
5.5 volts applied
to a
control
poft
can cause the CR500
to
malfunction.
Voltages
in
excess
of
8 VDC
can
cause damage.
Voltages
in
excess of
7 VDC applied
to
the
5
V
port
will
damage
the
CR500.
Voltage
pulses
can be counted
by
CR500
Pulse
Counters configured
for High
Frequency
Pulses. However,
when
the
pulse
is actually a
low frequency
signal
(below
about
10 Hz)AND the
positive
voltage excursion
exceeds 5.6
VDC,
the 5
VDC
supply
will start to
rise, upsetting
all
analog
measurements.
Pulses
whose
positive
voltage
portion
exceed
5.6
VDC with a duration
longer than
100
milliseconds
need external
conditioning.
See
below.
FIGURE.
Conditioning
for Long
Duration
Voltage Pulses
7.
4.
ilt